Understand the Importance Of Correct Cooling Tower Fill

15 Mar.,2024

 

Types Of Fill

Figure 2. Choice of fill largely depends on the fouling tendencies of the cooling water. Source: Brentwood Industries.

Offset flutes (OF, 2e) also have high specific surface area, and force the water and air through a moderately tortuous path. Thus, anti-fouling characteristics are moderate, too.
Cross flutes (CF, 2f) typically provide high specific surface area and high thermal performance but exhibit poor anti-fouling characteristics due to the geometry that forces many deviations to the flow path.

Flute spacing significantly affects fill performance; smaller spacing increases the surface area but also raises the potential severity of fouling.

Many investigators have pointed to bio deposits as the key trigger of film fill fouling. The scenario for fouling is: biofilms form on the fill surface and collect suspended solids from the cooling water due to the inherent adhesive properties of the bacterial secretions.

The velocity of the water film passing over the deposit surface influences the stability of bio deposits. Higher water velocities minimize biofilm thickness. So, fill manufacturers have developed designs that maximize water film velocity and the resulting high shear stress. The flute geometry of these low fouling fills has a vertical orientation as opposed to the angled orientation (cross flute) of high efficiency fills. These higher water velocity designs exhibit lower thermal performance than their CF counterparts.

CF fills provide maximum surface area for heat transfer but impart a higher pressure drop through the tower than other designs. Also, the lower water film velocity developed within these fills can lead to low flow regions, increasing the fouling potential.

Selecting the proper design requires a careful evaluation of water conditions. Table 1 outlines guidelines for fill selection with various quality waters, ranging from <1,000 ppm to <25 ppm of total suspended solids (TSS) and 0 to <50 ppm of oil and grease.

That table underscores the impact of biological control on fill selection. Yet, as I personally can attest, microbiological control in cooling systems, even once-through networks, can be a challenge. However, suitable care in the design and selection of chemical feed programs and makeup-water pretreatment equipment may enable use of higher-efficiency fills in applications where they otherwise wouldn’t make sense.

Oxidizing biocide treatment is essential for all cooling water systems. Chlorine, usually supplied as bleach or generated on-site, is the most common choice, although the effectiveness of chlorine rapidly diminishes as the pH rises above 7.5. Many natural waters have a pH near 8, which often leads to selection of alternative oxidizers, most notably chlorine-activated bromine, chlorine dioxide, monochloramine and monobromamine. In many cases, oxidizer feed is limited to two hours per day, which gives microbes time to settle and form colonies during off times. A supplemental feed of a non-oxidizing biocide, say, on a once-per-week basis, can quite effectively control microorganisms. Table 2 lists properties of some of the most common non-oxidizers.

Careful evaluation of the microbial species in the cooling water is necessary to determine the most effective biocides. Do not test, let alone use, any of these chemicals without approval from the appropriate regulating agency. They must be incorporated into the plant’s National Pollutant Discharge Elimination System permit. Also, as with all chemicals, safety is an absolutely critical issue when handling the non-oxidizers.

Other Factors

The use of alternatives to fresh water for plant makeup is becoming more common. One increasingly popular source, either by choice or mandate, is effluent from a publicly owned treatment works, i.e., municipal wastewater treatment plant discharge. These streams often have significant concentrations of ammonia, nitrite/nitrate, phosphate and organics, or in the industry vernacular, “bug food.” Untreated, such makeup water can cause explosive growth of microorganisms in cooling systems. Sophisticated pretreatment of the plant makeup usually is necessary, with two increasingly common options being membrane bioreactors and moving-bed bioreactors.

Another factor that influences fouling is the suspended solids’ concentration in the water. Any microbiological colonies that do become established in fill or heat exchangers typically secrete a slimy film for protection. This slime naturally captures silt. A treatment method that is regularly recommended for cooling towers — but often isn’t adopted — is sidestream filtration. Information about sidestream filtration is readily available from a number of sources, most notably the Cooling Technology Institute.

BRAD BUECKER is a senior technical publicist for ChemTreat, Glen Allen, Va. Email him at [email protected].

ACKNOWLEDGEMENTS

The author wishes to acknowledge Rich Aull, retired from Brentwood Industries and now president of Richard Aull Cooling Tower Consulting, LLC, for providing substantial assistance with this article, and Bill Miller of Brentwood Industries for photos of the various types of fill.

REFERENCES
1. Zaorski, A. and W.C. Miller, “A Study on Bio-Fouling Characteristics of Contemporary Trickle and Modular Splash Fills,” presented at the 2017 Cooling Technology Institute Annual Conference, New Orleans, La. (February 2017).
2. Wallis, J. and R. Aull, “Improving Cooling Tower Performance with Thermal Fills,” Process Cooling & Equipment, March/April 2000.